L8148J1009/U Aquastat Relay, 120 – 240 °F Range with 8 °F Fixed Differential, Low Volt/Millivolt

Part Number: L8148J1009/U Brand: Resideo Technologies Inc

Aquastat Relay, 120 – 240 F Range with 8 Degree F Fixed Differential, Low Volt/Millivolt

Price
Request a Quote
Stock
In Stock
Does not ship to VA, United States

Immersion-type controllers that combine high limit protection with switching relay control of burner and circulator motors.
Features
  • High Limit Opens Burner Circuit Only.
  • Select Models Include Transformer and Accessory Terminals for Adding a Remote Low Limit Controller.
  • Case Available for Horizontal or Vertical Mounting.
  • Requires a 24 Vac Thermostat with Heat Anticipator Set at 0.2A.
  • Tradeline Models Include Well Adapter, Tube of Heat Conductive Compound and Range Stops

Specifications

Hazmat Information

  • UN 1294, TOLUENE, 3, II

Dimensions

  • Vertical Mount: 6 1/8 in. high x 4 5/16 in. wide x 3 1/8 in. deep; Horizontal Mount: 4 5/16 in. high x 6 1/8 in. wide x 3 1/8 in. deep
  • Vertical Mount 156 mm high x 110 mm wide x 79 mm deep; Horizontal Mount: 110 mm high x 156 mm wide x 79 mm deep

Maximum Safe Operating Pressure

  • Immersion Well: 255 psi
  • Immersion Well: 1757 kPa

Temperature Range

  • Maximum: 150 °F with 1.2 A 24 V load; 77 °F with 1.4 A 24 V load
  • Maximum: 66 °C with 1.2 A 24 V load; 25 °C with 1.4 A 24 V load

Mounting

  • Horizontal or Vertical

Electrical Ratings

  • Low Voltage:0.8 A max. @ 24 Vac; Millivolt:0.25 A @ 1/4 to 12 Vdc

Frequency

  • 60 Hz

Approvals, Underwriters Laboratories Inc.

  • UL Listed: File No. MP466, Vol. 13, Sec. 2, Guide No. MBPR2.

Approvals, Canadian Standards Association

  • Certified: File No. LR1620, Guide No. 400-E-O

Tradeline Value

  • Tradeline

Electrical Connections

  • Quick-Connect / Screw

Operating Humidity Range

  • 0 to 95% RH, non-condensing

Voltage

  • 120 Vac

Operating Temperature Range

  • High Limit: 120 °F to 240 °F
  • High Limit: 54 °C to 116 °C

Differential Temperature

  • 8 °F fixed

Switching Action

  • SPST: High Limit & Circulator

Anticipator Setting

  • 0.2 A

Capillary Length

  • 4-1/2 in.
  • 114 mm

Insulation Depth

  • 1-1/2 in. to 3 in. less well
  • 38 mm to 76 mm less well

Electrical Ratings, Burner

  • At Full Load - Low Voltage: 0.8 A max. @ 24 Vac: Line Voltage: 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor - Line Voltage: 44.4 A @ 120 Vac: 22.7 A @ 240 Vac

Electrical Ratings, Circulator

  • At Full Load - 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor - 44.4 A @ 120 Vac: 22.2 A @ 240 Vac

  • Aquastat Relay

show more