  • Lockout Time: 4 - 15 seconds
  • 120 Volt Igniter and Blower Motor Output: Yes
  • 24 Volt Gas Valve Output: Yes
  • 2 Pin Connector for Pressure Switch: No
  • Non-Volatile Lockout: No

Specifications

Input Voltage

  • 120 V, 50/60 Hz (igniter, motor)
  • 24 V (18-30 VAC) 50/60 Hz (gas valve and air proving switch)

Current Draw - Run

  • 0.2 Amps (Control Only)

Output

  • Main Valve Rating: 2.0 amps
  • Motor Relay Rating: 7.4 amps (120 V)
  • Igniter Relay Rating: 1.0 amp (120 V)

Approvals

  • UL listing per ANSI Z21.20, UL372 and CSA C22.2 No. 199

Timings

  • Ignition Timing: 4-15 seconds
  • Pre-purge Timing: 1-240 seconds
  • Inter-purge Timing: 90-300 seconds

Additional Ratings

  • Minimum Flame Current Required: 1.0 µA
  • Flame Failure Response Time: 0.8 seconds (maximum)
  • Thermostat Voltage: 24 Vac (if used)
  • Heat Anticipator Setting: 0.2 amps + gas valve current draw (control is not polarity sensitive)

Environmental Ratings

  • Storage & Operating Ambient Temperature: -40°F to +175°F (-40°C to +79.4°C)
  • Moisture: 5 to 95% RH, non-condensing

show more